© 2008 D 264 - 12/08 10 of 32
OUTDOOR DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air temperature that is the typical coldest temperature of the year where the building is
located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected,
the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the
boiler supply temperature rises rapidly as the outdoor temperature drops.
BOIL MAX
BOIL DSGN
OUT DSGN
ROOM Occ
ROOM UnOcc
210
(99)
190
(88)
170
(77)
150
(66)
130
(54)
110
(43)
90
(32)
70
(2
50°F
(10°C)
-20
(-29)
0
(-18)
20
(-7)
40
(5)
60
(16)
80
(27)
Outdoor Air Temperature
Supply Water Temperature
Boiler Characterized
Heating Curve
Boiler Characterized
Heating Curve
BOIL MIN
BOIL IND
WWSD Occ
WWSD UnOcc
TERMINAL UNIT
HIGH MASS RADIANT
(1)
LOW MASS RADIANT
(2)
FANCOIL
(3)
FIN-TUBE CONVECTOR
(4)
RADIATOR
(5)
BASEBOARD
(6)
BOIL DSGN
BOIL MAX
BOIL MIN
120°F (49°C)
140°F (60°C)
OFF
140°F (60°C)
160°F (71°C)
OFF
190°F (88°C)
210°F (99°C)
140°F (60°C)
180°F (82°C)
200°F (93°C)
140°F (60°C)
160°F (71°C)
180°F (82°C)
140°F (60°C)
150°F (66°C)
170°F (77°C)
140°F (60°C)
High Mass Radiant (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum
pour. This heating system has a large thermal mass and is slow acting.
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor,
suspended in the joist space, or sandwiched between the sub-floor and the surface.
This type of radiant system has a relatively low thermal mass and responds faster than
a high mass system.
BOILER DESIGN TEMPERATURE
The boiler design temperature is the supply water temperature required
to heat the building when the outdoor air temperature is as cold as the
outdoor design temperature.
WARM WEATHER SHUT DOWN
When the outdoor air temperature rises above the WWSD setting, the
control turns on the WWSD pointer in the display. When the control is in
Warm Weather Shut Down, the boiler demand pointer is displayed if there
is a boiler demand. However, the control does not operate the heating
system to satisfy this demand. The control does respond to a DHW or a
setpoint demand and operates as described in section E or F.
ROOM
The room is the desired room temperature for the building and provides a parallel shift of the heating curve. The room temperature
desired by the occupants is often different from the design indoor temperature. If the room temperature is not correct, adjusting
the ROOM setting increase or decreases the amount of heat available to the building. A ROOM setting is available for both the
occupied (day) and unoccupied (night) periods.
TERMINAL UNITS
The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-
tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply
temperature, maximum supply temperature, and minimum supply temperature. The factory defaults are listed below. These
factory defaults can be changed to better match the installed system. If a factory default has been changed, refer to section A
to reload the factory defaults.
Przeglądanie stron 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 31 32

Komentarze do niniejszej Instrukcji

Brak uwag

AEG Electrolux 41056VI-MN 24T manuales

Manuales del propietario y guías del usuario para Hornos AEG Electrolux 41056VI-MN 24T.
Ofrecemos 1 manuales en pdf AEG Electrolux 41056VI-MN 24T para descargar gratis por tipos de documentos: Manual de usuario






Más productos y manuales para Hornos AEG Electrolux

Modelos Tipo de documento
E10003-5-D DE R08 Manual de usuario   Aeg-Electrolux E10003-5-M DE R08 Benutzerhandbuch, 48 paginas
E30512-4-W DE R07 Manual de usuario   Aeg-Electrolux E30512-4-W DE R07 Benutzerhandbuch, 44 paginas
E33519-5-W Manual de usuario   Aeg-Electrolux E33519-5-M Benutzerhandbuch [hr] [sk] [sk] , 28 paginas
EE3013031M Manual de usuario   Aeg-Electrolux EE3013031M Benutzerhandbuch [mk] , 32 paginas
E8931-4-A NORDIC R0 Manual de usuario   Aeg-Electrolux E8931-4-A NORDIC R0 User Manual, 68 paginas
EP7304031M Manual de usuario   Aeg-Electrolux EP7304031M Benutzerhandbuch, 32 paginas
EP3003031M Manual de usuario   Aeg-Electrolux EP3003031M Benutzerhandbuch [mk] , 32 paginas
E8831-7-M Manual de usuario   Aeg-Electrolux E8831-7-M Benutzerhandbuch, 36 paginas
E3051-4-M DE R07 Manual de usuario   Aeg-Electrolux E3051-4-W DE R07 User Manual [de] , 48 paginas
EE5003011M Manual de usuario   Aeg-Electrolux EE5003011M Benutzerhandbuch [en] [es] , 32 paginas
E9871-7-M Manual de usuario   Aeg-Electrolux E9871-7-M User Manual [pl] , 28 paginas
EE5303151M Manual de usuario   Aeg-Electrolux EE5303151M Benutzerhandbuch [fr] , 36 paginas
41056VH-MN 23T Manual de usuario   Aeg-Electrolux 41056VH-MN 23T Benutzerhandbuch [ja] , 64 paginas
BC3003001M Manual de usuario   Aeg-Electrolux BC3003001M Benutzerhandbuch, 28 paginas
B8875-5-M Manual de usuario   Aeg-Electrolux B8875-5-M Benutzerhandbuch, 36 paginas
E3191-4-M R05 Manual de usuario   Aeg-Electrolux E3191-4-M R05 Benutzerhandbuch [ro] , 48 paginas
88101K-MN 00P Manual de usuario   Aeg-Electrolux 88101K-MN 00P Benutzerhandbuch [en] , 32 paginas
BE4314021M Manual de usuario   Aeg-Electrolux BE4314021M Benutzerhandbuch [it] , 32 paginas
E42042-6-M Manual de usuario   Aeg-Electrolux E42042-6-M Benutzerhandbuch [sk] , 28 paginas
E9971-5-M Manual de usuario   Aeg-Electrolux E9971-5-M Benutzerhandbuch, 64 paginas